DR Series Single Output Industrial DIN Rail Power Supply

  • 120W Single Output Industrial DIN Rail Power Supply (Model: DR-120-12/24/48)
120W Single Output Industrial DIN Rail Power Supply (Model: DR-120-12/24/48)

120W Single Output Industrial DIN Rail Power Supply (Model: DR-120-12/24/48)

  • Input: 85 ~ 264VAC 120 ~ 370VDC
  • Modulation System: PWM
  • MTBF: 432.1Khrs min. MIL-HDBK-217F (25'C)
  • Safety Standard: En60950
  • Description:
  • INQUIRY   EMAIL

DR Series Single Output Industrial DIN Rail Power Supply







Features

1. Universal AC input/Full range
2. Protections: Short circuit / Overload / Over voltage
3. Cooling by free air convection
4. Can be installed on DIN rail TS-35/7.5 or 15
5. Isolation class I
6. LED indicator for power on
7. 100% full load burn-in test
8. 2 years warranty


Technical Parameters

MODEL

DR-120-12

DR-120-24

DR-120-48

OUTPUT

DC VOLTAGE

12V

24 V

48V

RATED CURRENT

10A

5A

2.5A

CURRENT RANGE

0-10A

0-5A

0-2.5A

RATED POWER

120W

120W

120W

RIPPLE & NOISE (max.) Note.2

80mVp-p

80mVp-p

100mVp-p

VOLTAGE ADJ. RANGE

12- 14V

24-28V

48 - 53V

VOLTAGE TOLERANCE Note.3

±2.0%

±1.0%

±1.0%

LINE REGULATION

±0.5%

±0.5%

±0.5%

LOAD REGULATION

±1.0%

±1.0%

±1.0%

SETUP, RISE TIME

500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load

HOLD UP TIME (Typ.)

36ms/230VAC 32ms/115VAC at full load

INPUT

VOLTAGE RANGE

85 ~ 264VAC 120 ~ 370VDC

FREQUENCY RANGE

47~63Hz

EFFICIENCY (Typ.)

80%

84%

85%

AC CURRENT (Typ.)

2.6A/115VAC 1.6A/230VAC

INRUSH CURRENT (Typ.)

COLD START 20A/115VAC 40A/230VAC

LEAKAGE CURRENT

<3.5mA/240VAC

PROTECTION

OVERLOAD

105 -150% rated output power

Protection type: Constant current limiting, recovers automatically after fault condition is removed

OVERVOLTAGE

15-16.5V

29 - 33V

58 -65V

Protection type: Shut down o/p voltage, re-power on to recover

OVER TEMPERATURE

85"C ±5"C (TSW1)

90"C+5"C(TSW1)

90'C ±5"C(TSW1)

Protection type: Shut down o/p voltage, recovers automatically after temperature goes down

ENVIRONMENT

WORKING TEMP.

-10 - +60"C (Refer to "Derating Curve")

WORKING HUMIDITY

20 - 90% RH non-condensing

STORAGE TEMP., HUMIDITY

-20 - +85 "C, 10 - 95% RH

TEMP. COEFFICIENT

±0.03%/"C (0-50'C)

VIBRATION

10 - 500Hz, 2G 10min./1 cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY &

EMC

(Note 4)

SAFETY STANDARDS

UL508, UL60950-1, TUV EN60950-1 approved

WITHSTAND VOLTAGE

l/P-0/P:3KVAC l/P-FG:1.5KVAC 0/P-FG:0.5KVAC

ISOLATION RESISTANCE

l/P-O/P, l/P-FG, 0/P-FG:100M Ohms/500VDC/25,C/70% RH

EMC EMISSION

Compliance to EN55011 .EN55022 (CISPR22) Class B, EN61000-3-2.-3

EMC IMMUNITY

Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A

OTHERS

MTBF

432.1Khrs min. MIL-HDBK-217F (25'C)

DIMENSION

65.5*125.2*100mm (W*H*D)

PACKING

0.79Kg; 20pcs/16.5Kg/1.29CUFT

NOTE

1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25'C of ambient temperature.

2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor.

3.Tolerance : includes set up tolerance, line regulation and load regulation.

4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.


Inquiry:

Categories

CONTACT US

Contact: Henry Zhou

Phone: +86-13626551830

Tel: +86-577-55773828

Whatsapp: +86-13626551830

Email: reelen@reelen.com.cn

Add: Xiangyang Industrial Zone,Liushi Town, Yueqing, Zhejiang, China. 325619